Level Tier 2
Certification CSAE 3416
Connected via Peer 1 FastFiber Network™
Address 20 Pullman Court, Scarborough, Toronto, Ontario M1X 1E4, Canada
Security Security card access and DVR camera systems
Backup and power UPS and diesel generator power systems N+1 Backup Power Systems

Technical Specifications

Power Main 26.7kV feeder capacity – 10MW
Secondary 26.7kV feeder provisions in place
Medium and high density power designed for 5-15+ kW per rack
UPS Current capacity, 10 x 750kVA UPSs (N+1)
Future capacity, 15 x 750kVA UPSs (N+1)
Battery runtime of 20 minutes at full load
Generator Current capacity, 5 x 2MW generators (N+1)
Future capacity, 6 x 2MW generators (N+1)
6 hour refueling agreement in place
48 hours of fuel capacity available at full load
Controlled Environment Current capacity, 5,276Kw (N+1)
Future capacity, 8,793Kw (N+1)
Condenser and chilled water pumps (N+1)
Chilled water based cooling system with onsite chilled water storage
“Free Cooling” heat exchangers in place
Onsite well in place for primary makeup water source with city water for redundancy (N+1)
Temperature and humidity in data centre space maintained to ASHRAE server inlet standards
Fire Detection & Suppression Monitored analogue addressable fire detection system in all areas
Photoelectric, ionization smoke sensors below and above floor
Dry-pipe preaction fi re suppression
Clean agent fire extinguishers deployed throughout the facility
Network Access to multiple communications providers
Multiple access building entry points for diverse routing
Complete Juniper solution with carrier-grade Juniper routers at the distribution – high packet processing capability, huge ACL and rate limiting, QOS/COS capability, IPv6 and MPLS, scalable
Redundant diverse 10Gbps backbone
Fully redundant switching architecture for true Non Stop Routing (NSR) and In Service Software Upgrade (ISSU)
Uses Virtual Router Redundancy Protocol (VRRP) for interoperability with other routing vendors
Juniper EX series switches with Virtual Chassis design – simplified network design, scalability, reliance and redundancy, robust power supply, massive capacity, auto reconfiguration, on board automation
Building Management Enterprise Building Management System in place, monitoring all aspects of infrastructure
24x7x365 building management and network monitoring team
Security External and internal HD CCTV cameras tied back to NVR systems
DVR system tied to backup SAN storage
Video records retained for 90 days
Proximity access control system in place utilizing access card and biometric authentication
Mantrap in place utilizing ultrasonic technology for single person verification
Intruder and door tampering alarms in place
Secure managed loading dock
24x7x365 manned DCO onsite
Green Strategy Data centre designed at full load to have a Power Usage Effectiveness (PUE) of 1.3 to 1.4
Well water to reduce demand on the city water system
Brand new eco-friendly Cool Roof
High efficiency cooling system designed to utilize free cooling throughout cooler months
Designed with highly efficient power and mechanical systems
Utilizing new highly efficient Emerson Liebert CRAC units with EC plug fans
Green initiative to encourage responsible energy use to maximize PUE.