Level Tier 2
Connected via Hurricane Electric
Address Equinix DA4, 2323 Bryan St., Suite 1400, Dallas, TX 75201
Security Mantrap, site personnel, CCTV and recorders, motion detection, HID with PIN readers
Backup and power 4 x 275 kVA parallel redundant (N+1) UPS with 1,500 kW diesel generator for backup

Technical Specifications

Power Electrical capacity: 2.4 kVA per cabinet
UPS configuration: 4 x 275 kVA parallel redundant (N+1)
Utility feeders: one
Power transformers: two
Utility voltage: 0.48 kV
Standby power: 1 x 1,500 kW diesel generators
Standby power: N
Controlled Environment Cooling capacity: 2.4 kVA (8,191 BTUH) per cabinet
Cooling plant: 200 tons evaporative cooled refrigeration system (N+1)
Fire Detection & Suppression Double-interlocked, pre-action (dry pipe)
Security Mantrap, site personnel, CCTV and recorders, motion detection, HID with PIN readers