Sydney

Overview

Level Tier 3
Connected via Equinix
Address 47 Bourke Road, Sydney, Australia, 2015

Technical Specifications

Power Electrical capacity (critical customer load) – 3.84 kVA per cabinet
Electrical capacity (uninterruptable power system) – 9 x active UPS electrical block +3 x redundant UPS electrical block
Power transformers – 6 x 2.25 MVA HV transformers + 4 x 2.25 MVA HV transformers
Power distribution – 6 x 11Kv/415 transformers + 4 x 11Kv/415 transformers
Standby power – 6 x 2.275 MVA prime-rated Caterpillar generator sets (N+1 block redundancy) + 4 x 2.275 MVA prime-rated Caterpillar generator sets (N+1 block redundancy)
Controlled Environment Cooling capacity – 3.84 kVA per cabinet
Cooling plant – 4 x chiller electrical block; 6 x 3.7 MWr chiller + 2 x 0.65 MWr chiller
CRAC Units – Phase 1: 32 x 126 Kw Stulz units serving colo halls in 3+1 configuration , Phase 2: 32 x 126 Kw Stulz units serving colo halls in 3+1 configuration, Phase 3: 32 x 126 Kw Stulz units serving colo halls in 3+1 configuration
Network System – Overhead proprietary fibre guide system; Overhead cable management system multi-tier ladder rack
Cross connects – CAT5, CAT6, COAX and fibre
Equinix Internet Exchange™ – Central switch for public and private peering offering fast Ethernet, gigabit Ethernet and 10-gigabit Ethernet
Equinix Connect – automated network provisioning, multi-homing and billing offering Fast Ethernet or Gigabit Ethernet
Security Physical – physical access control; security fencing; boom gates, Human – security officers at access points 24/7/365
Electronic – round-the-clock CCTV recordings; access control (mantraps); biometric readers at all main entry points
Human – security officers with fixed locations at front and rear access points, 24 hours a day, 7 days a week, 365 days a year