Florida – Miami

Overview

Level Tier 3
Connected via Hurricane Electric
Address Equinix MI3, 4680 Conference Way South, Suite 150, Boca Raton, FL33431
Security Mantrap, site personnel, CCTV and recorders, motion detection, HID with PIN readers
Backup and power 4 x 275 kVA parallel redundant (N+1) UPS with 5 x 2,000 kW diesel generator for backup

Technical Specifications

Power Electrical capacity – 4-6 kVA per cabinet
UPS configuration – N+1 block redundant
Utility feeders – 1
Power transformers – 1
Utility voltage – 0.48 kV
Standby power – 5 x 2,000 kW diesel engine generators
Standby power configuration – N+1
Controlled Environment Cooling capacity – 4 kVA per cabinet (13,652 BTUH)
Cooling plant – 600 tons 2N water-cooled centrifugal central system
Fire Detection & Suppression Double-interlocked, pre-action (dry pipe)
Security Mantrap, site personnel, CCTV and recorders, motion detection, HID with PIN readers